Re: size of fuse after a smart solar 100/50
10 AWG wire is rated for minimum 30 amp so the fuse was correct. However some back of the napkin math shows that the two 310W solar panels can exceed 30 amps after the charge controller in real world…2 -
Re: size of fuse after a smart solar 100/50
Fuses protect the wiring so simply putting in a larger fuse might cause wiring to get hot to the point of insulation melting. Check the wire gauge that is installed and make sure it can carry the cur…2 -
Re: Boondocking & Battery Life
A few comments: The Victron screen shows the amount of current going to the battery. With a fully charged battery that is pretty much equal to what the individual appliances consume. If the battery i…1 -
Re: 2024 TAB 320-S Black Canyon Factory Solar: Best Yield and Configuration?
From a theoretical perspective solar panel ratings are wildly optimistic as they are determined under very specific test conditions that do not reflect real world use. Typically the panels reach 75% …1 -
Re: No Heat coming from Alde 3020 system (May 2026)
Two things come to mind: During the inverter install something was changed so the Alde system does not receive AC power anymore. Or, the breaker for the Alde system is tripped.1